AcuLink 810 Data Aquisition Server

13.1.1 Rapid Logger

The AcuLink 810 supports the rapid logging function, where the user has the ability to log
data at intervals as fast as 1 second.
• Rapid Data Logger Enable: Select Enable to begin the rapid logging function
• Post Channel: Select the Post Channel from the drop-down list:
• None: AcuLink 810 will log and store the data on its memory
• Post Channel 1/2/3: AcuLink 810 will log and push the data to the configured post chan-
nel. Users will not be able to select the post channel if it is disabled.
• Timestamp Format: Select the format of the timestamp for the data that is logged. The
format for the timestamp can be based on the Local Time, UTC Seconds or based on
ISO8601 Format. An example of each time format is shown next to each setting.
• Log File Name Format: Select the format of the log file name for the data that is logged.
The format for the log file name can be based on UTC Timestamp or Time interval Format.
An example of each file name format is shown next to each setting.
• Log Interval: Select how frequently the module will log data to the file from the drop-
down list. The logging interval can be from 1 second to 30 seconds.
• Log File Length: Select the length of the log file, it can be from 1 minute to 1 month. The
log file length is in reference to the post channels sending interval, for example if the log
interval is 1 minute and the log file length is 5 minutes the log file will be sent to the exter-
nal server every 5 minutes. If the user is only configuring the logger to save data on the
810's internal memory the log file length setting is irrelevant and can be ignored.
• Log File Name Prefix: Provide a name for the log file which will be appended to the begin-
ning of the log file. By default the prefix for the rapid logger is loggerRapid.
• Devices: The user can select the device for the rapid logger.
NOTE: Only Modbus devices connected via RS485 can be logged using the Rapid Logger.
98
V: 1.08 Revised: May 2020
www.accuenergy.com