Operating Guide | VLT® HVAC Drive FC 102

7 Wiring Configuration Examples

7.1 Application Examples

The examples in this section are intended as a quick reference for common applications.
Parameter settings are the regional default values unless otherwise indicated (selected in parameter 0-03 Regional Settings).
Parameters associated with the terminals and their settings are shown next to the drawings.
Required switch settings for analog terminals A53 or A54 are also shown.

7.1.1 Wiring Configuration for Automatic Motor Adaptation (AMA)

Table 16: Wiring Configuration for AMA with T27 Connected
Drive
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Danfoss A/S © 2020.01
Parameters
Function
Parameter 1-29 Automatic Motor Adaptation (AMA)
Parameter 5-12 Terminal 27 Digital Input
*=Default value
Notes/comments:
Set parameter group 1-2* Motor Data according to motor nameplate.
Wiring Configuration Examples
Setting
[1] Enable complete AMA
[2]* Coast inverse
AQ275556502253en-000101 / 130R0706| 73