Operating Guide | VLT® HVAC Drive FC 102
Motors with class d/e protection
The motor itself has an e ignition protection class, while the motor cabling and connection environment are in compliance with the d
classification. To attenuate the high peak voltage, use a sine-wave filter at the drive output.
MOTOR THERMISTOR SENSOR MONITORING
Units with the VLT® PTC Thermistor Card MCB 112 option are PTB-certified for potentially explosive atmospheres.
4.4 Installation Requirements
OVERHEATING
Improper mounting can result in overheating and reduced performance.
Install the drive according to the installation and cooling requirements.
-
•
Locate the unit as near to the motor as possible. See
•
Ensure unit stability by mounting the unit to a solid surface.
•
Enclosures E3h and E4h can be mounted:
-
Vertically on the back plate of the panel (the typical installation).
-
Vertically upside down on the back plate of the panel. Consult the factory.
-
Horizontally on its back, mounted on the back plate of the panel. Consult the factory.
-
Horizontally on its side, mounted on floor of the panel. Consult the factory.
•
Ensure that the strength of the mounting location supports the unit weight.
•
Ensure that there is enough space around the unit for proper cooling. Refer to
•
Ensure enough access to open the door.
•
Ensure cable entry from the bottom.
4.5 Cooling Requirements
OVERHEATING
Improper mounting can result in overheating and reduced performance.
Install the drive following the installation and cooling requirements.
-
•
Ensure that top and bottom clearance for air cooling is provided. Clearance requirement: 225 mm (9 in).
•
Provide sufficient airflow flow rate. See
•
Consider derating for temperatures starting between 45 °C (113 °F) and 55 °C (131 °F) and elevation 1000 m (3300 ft) above sea
level. For more information, see the product-specific design guide.
The drive utilizes a back-channel cooling concept that removes heat sink cooling air. The heat sink cooling air carries approximately
90% of the heat out of the back channel of the drive. Redirect the back-channel air from the panel or the room by using either:
24 | Danfoss A/S © 2020.01
N O T I C E
N O T I C E
9.5 Cable Specifications
N O T I C E
4.6 E1h-E4h Airflow
Rates.
Mechanical Installation
for the maximum motor cable length.
9.9 Enclosure
Airflow.
AQ275556502253en-000101 / 130R0706