4.4 Installation Requirements

OVERHEATING
Improper mounting can result in overheating and reduced performance.
Install the drive according to the installation and cooling requirements.
-
Locate the unit as near to the motor as possible. See
Ensure unit stability by mounting the unit to a solid surface.
Enclosures E3h and E4h can be mounted:
-
Vertically on the back plate of the panel (the typical installation).
-
Vertically upside down on the back plate of the panel. Consult the factory.
-
Horizontally on its back, mounted on the back plate of the panel. Consult the factory.
-
Horizontally on its side, mounted on floor of the panel. Consult the factory.
Ensure that the strength of the mounting location supports the unit weight.
Ensure that there is enough space around the unit for proper cooling. Refer to
Ensure enough access to open the door.
Ensure cable entry from the bottom.

4.5 Cooling Requirements

OVERHEATING
Improper mounting can result in overheating and reduced performance.
Install the drive following the installation and cooling requirements.
-
Ensure that top and bottom clearance for air cooling is provided. Clearance requirement: 225 mm (9 in).
Provide sufficient airflow flow rate. See
Consider derating for temperatures starting between 45 °C (113 °F) and 55 °C (131 °F) and elevation 1000 m (3300 ft) above sea
level. For more information, see the product-specific design guide.
The drive utilizes a back-channel cooling concept that removes heat sink cooling air. The heat sink cooling air carries approximately
90% of the heat out of the back channel of the drive. Redirect the back-channel air from the panel or the room by using either:
24 | Danfoss A/S © 2020.01
N O T I C E
N O T I C E
9.5 Cable Specifications
N O T I C E
4.6 E1h-E4h Airflow
Rates.
Mechanical Installation
for the maximum motor cable length.
9.9 Enclosure
Airflow.