Operating Guide | VLT® HVAC Drive FC 102
FC 102
Enclosure size
Output current (3-phase)
Continuous (at 525 V) [A]
Intermittent (60 s overload) (at 525 V) [A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/690 V) [A]
Continuous kVA (at 525 V) [kVA]
Continuous kVA (at 575 V) [kVA]
Continuous kVA (at 690 V) [kVA]
Maximum input current
Continuous (at 525 V) [A]
Continuous (at 575/690 V) [A]
Maximum number and size of cables per phase (E1h/E2h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
2
- Brake or regen [mm
(AWG)]
Maximum number and size of cables per phase (E3h/E4h)
2
- Mains and motor [mm
(AWG)]
2
- Brake [mm
(AWG)]
- Load share or regen [mm
Maximum external mains fuses [A]
Estimated power loss at 600 V [W]
Estimated power loss at 690 V [W]
Efficiency
(3)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
1
9.7 Fuses
For fuse ratings, see
.
2
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
Danfoss A/S © 2020.01
2
(AWG)]
2
(AWG)]
2
(AWG)]
(1)
(2) (3)
(2) (3)
N630
E1h/E3h
630
693
630
693
573
627
753
607
607
5x240 (5x500 mcm)
6x240 (5x500 mcm)
4x240 (4x500 mcm)
5x240 (4x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
800
8676
8915
0.98
0–590
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
AQ275556502253en-000101 / 130R0706| 131
Specifications
N710
N800
E2h/E4h
E2h/E4h
763
889
839
978
730
850
803
935
694
808
727
847
872
1016
735
857
704
819
6x240 (5x500 mcm)
5x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
1200
1200
9709
11848
10059
12253
0.98
0.98
0–590
0–590
110 (230)
110 (230)
80 (176)
80 (176)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)

Advertisement