Operating Guide | VLT® HVAC Drive FC 102
Table 47: Disconnect Switch SCCR Requirements
Input voltage (V)
380–480
380–480
525–690
525–690
Danfoss A/S © 2020.01
Model
Short circuit rating (A)
N355–N450
42000
100000
N500–N560
42000
100000
N450–N630
42000
100000
N710–N800
42000
100000
Specifications
Required protection
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A
Circuit breaker
Class L fuse, 800 A
Circuit breaker
Class L fuse, 1200 A