Application Set-up Examples

6 Application Set-up Examples
The examples in this section are intended as a quick
reference for common applications.
Parameter settings are the regional default values
unless otherwise indicated (selected in
0-03 Regional Settings).
Parameters associated with the terminals and
their settings are shown next to the drawings.
Where switch settings for analog terminals A53 or
A54 are required, these are also shown.
NOTICE!
When the optional Safe Torque Off feature is used, a
jumper wire may be required between terminal 12 (or
13) and terminal 37 for the adjustable frequency drive to
operate when using factory default programming values.
6.1 Application Examples
6.1.1 AMA
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.1 AMA with T27 Connected
MG33AN22
Instruction Manual
Parameters
Function
Setting
1-29 Automatic
Motor
[1] Enable
Adaptation
complete
(AMA)
AMA
5-12 Terminal 27
[2]* Coast
Digital Input
inverse
* = Default Value
Notes/comments:
Parameter group 1-2* must be
set according to motor
D IN 37 is an option.
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.2 AMA without T27 Connected
Parameters
Function
Setting
1-29 Automatic
Motor
[1] Enable
Adaptation
complete
(AMA)
AMA
5-12 Terminal 27
[0] No
Digital Input
operation
* = Default Value
Notes/comments:
Parameter group 1-2* must be
set according to motor
D IN 37 is an option.