Operating Guide | VLT® HVAC Drive FC 102
8.4.83 ALARM 88, Option Detection
Cause
A change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has
been changed.
Troubleshooting
To apply the change, enable option layout changes in parameter 14-89 Option Detection.
Alternatively, restore the correct option configuration.
8.4.84 WARNING 89, Mechanical Brake Sliding
Cause
The hoist brake monitor detects a motor speed exceeding 10 RPM.
8.4.85 ALARM 90, Feedback Monitor
Troubleshooting
Check the connection to the encoder/resolver option and, if necessary, replace the VLT
Input MCB 103.
8.4.86 ALARM 91, Analog Input 54 Wrong Settings
Troubleshooting
Set switch S202 in position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54.
8.4.87 ALARM 99, Locked Rotor
Cause
The rotor is blocked.
Troubleshooting
Check if the motor shaft is locked.
Check if the start current triggers the current limit set in parameter 4-18 Current Limit.
Check if it increases the value in parameter 30-23 Locked Rotor Detection Time [s].
8.4.88 WARNING/ALARM 104, Mixing Fan Fault
Cause
The fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is turned on. The
mixing fan fault can be configured as a warning or an alarm in parameter 14-53 Fan Monitor.
120 | Danfoss A/S © 2020.01
Maintenance, Diagnostics, and
Troubleshooting
®
Encoder Input MCB 102 or VLT
AQ275556502253en-000101 / 130R0706
®
Resolver