Operating Guide | VLT® HVAC Drive FC 102
Table 21: Speed Up/Down
Drive
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 39:
Speed Up/Down
76 | Danfoss A/S © 2020.01
Parameter
Function
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-13 Terminal 29 Digital Input
Parameter 5-14 Terminal 32 Digital Input
*=Default value
Notes/comments:
D IN 37 is an option.
Wiring Configuration Examples
Setting
[8] Start*
[19] Freeze Reference
[21] Speed Up
[22] Speed Down