Parameter details
Parameter
Setting
Number
9
0 to 500A
71 (Note1)
83
0 to 1000V
84
50 to 120HZ
90
0 to, 9999
91
0 to, 9999
92
0 to, 9999
93
0 to, 9999
94
0 to 100%
96 (Note2)
Note: 1. The electronic overcurrent protection characteristics are also selected simultaneously.
2. Select "101" to increase tuning accuracy.
(2) Tuning execution
• For PU operation, press the
• For external operation, switch on the run command.
Note: 1. When "101" is set in Pr. 96, guard against hazards because the motor rotates.
2. To force tuning to end
• Switch on the MRS or RES signal or press the
• Switch off the tuning start command or make a forced stop.
3. During offline auto tuning, the following I/O signals are only valid:
• Input signals
STOP, OH, MRS, RT, CS, RES, STF, STR
• Output signals
RUN, OL, IPF, FM, AM, A, B, C
4. Special caution should be exercised when a sequence has been designed to open the
mechanical brake with the RUN signal.
5. When executing offline auto tuning, give the run command after switching on the main circuit
power supply (R, S, T) of the inverter.
Set the rated motor current (A).
0
Electronic overcurrent protection thermal characteristics suitable for standard motor
Electronic overcurrent protection thermal characteristics suitable for Mitsubishi
1
constant-torque motor
Electronic overcurrent protection thermal characteristics suitable for standard motor5-
2
point flexible V/F characteristics
Mitsubishi SF-JR4P standard motor (1.5kW or less), electronic overcurrent protection
20
thermal characteristics for advanced magnetic flux vector control
3
Standard motor
13
Constant-torque motor
Mitsubishi SF-JR4P standard motor
23
(1.5kW or less)
4
Standard motor
14
Constant-torque motor
Mitsubishi SF-JR4P standard motor
24
(1.5kW or less)
5
Standard motor
15
Constant-torque motor
6
Standard motor
16
Constant-torque motor
7
Standard motor
17
Constant-torque motor
8
Standard motor
18
Constant-torque motor
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
Tuning data
(Values measured by offline auto tuning are set automatically.)
9999
0
Offline auto tuning is not performed.
1
Offline auto tuning is performed without motor running.
101
Offline auto tuning is performed with motor running.
or
key.
FWD
REV
Get other manuals https://www.bkmanuals.com
Description
Select "offline auto tuning setting"
Auto tuning read or change setting
enabled
Star connection
Delta connection
Star connection
Delta connection
STOP
key to end.
RESET
120
PARAMETERS
Direct input of
motor constants
enabled
Direct input of
motor constants
and offline auto
tuning