Mitsubishi Electric FR-A520-0.4K Instruction Manual page 3

Hide thumbs Also See for FR-A520-0.4K:
Table of Contents

Advertisement

4. Additional instructions
Also note the following points to prevent an accidental failure, injury, electric shock, etc.
(1) Transportation and installation
When carrying products, use correct lifting gear to prevent injury.
Do not stack the inverter boxes higher than the number recommended.
Ensure that installation position and material can withstand the weight of the inverter. Install according to the information in the
Instruction Manual.
Do not operate if the inverter is damaged or has parts missing.
Do not hold the inverter by the front cover; it may fall off.
Do not stand or rest heavy objects on the inverter.
Check the inverter mounting orientation is correct.
Prevent screws, wire fragments, conductive bodies, oil or other flammable substances from entering the inverter.
Do not drop the inverter, or subject it to impact.
Use the inverter under the following environmental conditions:
Ambient temperature
Ambient humidity
Storage temperature
Ambience
Altitude, vibration
*Temperatures applicable for a short time, e.g. in transit.
(2) Wiring
Do not fit capacitive equipment such as a power factor correction capacitor, surge suppressor or radio noise filter (option FR-BIF)
to the inverter output side.
The connection orientation of the output cables (terminals U, V, W) to the motor will affect the direction of rotation of the motor.
(3) Trial run
Check all parameters, and ensure that the machine will not be damaged by a sudden start-up.
(4) Operation
When you have chosen the retry function, stay away from the equipment as it will restart suddenly after an alarm stop.
The [STOP] key is valid only when the appropriate function setting has been made. Prepare an emergency stop switch separately.
Make sure that the start signal is off before resetting the inverter alarm. A failure to do so may restart the motor suddenly.
The load used should be a three-phase induction motor only. Connection of any other electrical equipment to the inverter output
may damage the equipment.
Do not modify the equipment.
The electronic overcurrent protection does not guarantee protection of the motor from overheating.
Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.
Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic equipment may be affected.
Take measures to suppress harmonics. Otherwise power harmonics from the inverter may heat/damage the power capacitor and
generator.
When a 400V class motor is inverter-driven, it should be insulation-enhanced or surge voltages suppressed. Surge voltages
attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor.
When parameter clear or all clear is performed, each parameter returns to the factory setting. Re-set the required parameters
before starting operation.
The inverter can be easily set for high-speed operation. Before changing its setting, examine the performance of the motor and
machine.
In addition to the inverter's holding function, install a holding device to ensure safety.
Before running an inverter which had been stored for a long period, always perform inspection and test operation.
CAUTION
Constant torque: -10°C to +50°C (non-freezing)
(-10°C to +40°C with totally ecclosed structure specification attachment (FR-A5CV
Variable torque: -10°C to +40°C (non-freezing)
(-10°C to +30°C with totally ecclosed structure specification attachment (FR-A5CV
90%RH or less (non-condensing)
-20°C to +65°C*
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum 1000m above sea level for standard operation.
After that derate by 3% for every extra 500m up to 2500m (91%).
2
5.9 m/s
or less (conforming to JIS C 0040)
CAUTION
CAUTION
CAUTION
CAUTION
A-2
Get other manuals https://www.bkmanuals.com
))
))

Advertisement

Table of Contents
loading

Table of Contents