Mitsubishi Electric FR-A520-0.4K Instruction Manual page 36

Hide thumbs Also See for FR-A520-0.4K:
Table of Contents

Advertisement

<Wiring method>
1) Wiring of one RS-485 computer and one inverter
Computer Side Terminals
Signal name
Description
RDA
Receive data
RDB
Receive data
SDA
Send data
SDB
Send data
RSA
Request to send
RSB
Request to send
CSA
Clear to send
CSB
Clear to send
SG
Signal ground
FG
Frame ground
2) Wiring of one RS-485 computer and "n" inverters (several inverters)
Computer
RDA
RDB
SDA
SDB
RSA
RSB
CSA
CSB
SG
FG
Note: 1. Make connections in accordance with the instruction manual of the computer used.
Fully check the terminal numbers of the computer as they differ between models.
2. There may be the influence of reflection depending on the transmission speed and/or
transmission distance. If this reflection hinders communication, provide a terminal resistor. If the
PU connector is used to make a connection, use a distributor as a terminal resistor cannot be
fitted. Connect the terminal resistor only to the inverter remotest from the computer. (Terminal
resistor: 100Ω)
Cable connection and signal direction
10BASE-T Cable
(Note 1)
Cable connection and signal direction
10BASE-T Cable
(Note 1)
SG
Station 1
Inverter
27
Get other manuals https://www.bkmanuals.com
INSTALLATION AND WIRING
2
0.3mm or more
SG
SG
Station 2
Station n
Inverter
Inverter
Inverter
PU connector
SDA
SDB
RDA
RDB
SG
Termination
resistor
(Note 2)
2

Advertisement

Table of Contents
loading

Table of Contents