Parameters Recommended To Be Set By The User - Mitsubishi Electric FR-A520-0.4K Instruction Manual

Hide thumbs Also See for FR-A520-0.4K:
Table of Contents

Advertisement

4.1.3

Parameters recommended to be set by the user

We recommend the following parameters to be set by the user.
Set them according to the operation specifications, load, etc.
Parameter
Number
1
Maximum frequency
2
Minimum frequency
7
Acceleration time
8
Deceleration time
Second acceleration/deceleration
44
time
45
Second deceleration time
110
Third acceleration/deceleration time
111
Third deceleration time
9
Electronic thermal O/L relay
14
Load pattern selection
71
Applied motor
73
0-5V/0-10V selection
156
Stall prevention operation selection
900
FM terminal calibration
901
AM terminal calibration
902
Frequency setting voltage bias
903
Frequency setting voltage gain
904
Frequency setting current bias
905
Frequency setting current gain
Name
Used to set the maximum and minimum output frequencies.
Used to set the acceleration and deceleration times.
Used to set the current of the electronic overcurrent protection to protect the
motor from overheat.
Used to select the optimum output characteristics which match the
application and load characteristics.
Used to set the thermal characteristics of the electronic overcurrent
protection according to the motor used.
Used to select the specifications of the frequency setting signal entered
across terminal 2-5 to perform operation with the voltage input signal.
For the lift application, make setting to disable high-response current
restriction. Otherwise the torque may not be generated, rersulting in the lift
drop with gravity.
Used to calibrate the meters connected across terminals FM-SD and AM-5.
Used to set the magnitude (slope) of the output frequency relative to the
frequency setting signal (0 to 5V, 0 to 10V or 4 to 20mA DC) as desired.