Units
Terminal Connections
1, 2, 3...
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
C200HW-PA204: AC Input
1. AC Input
2.
Voltage selector
terminals
3. LG
4. GR
NC
C200HW-PA204R: AC Input
1. AC Input
2.
Voltage selector
terminals
3. LG
4. GR
7. RUN output
C200HW-PA204C
1. AC Input
3. LG
4. GR
8. Alarm output
1. AC Input (C200HW-PA20jj Only)
Supply either 100 to 120 VAC or 200 to 240 VAC to the AC input terminals. If
one power supply phase of the equipment is grounded, connect the
grounded phase side to the L
Supply 100 to 240 VAC to the C200HW-PA204C.
2. Voltage Selector Terminals (C200HW-PA20jj Only)
Short these terminals with a metal short bar when 100 to 120 VAC is being
supplied to the AC input terminals.
The C200HW-PA204C has a wide-range supply voltage, so voltage selec-
tor terminals are not provided.
C200HW-PA204S: AC Input
L
/N
2
100 to 120 VAC/
1. AC Input
200 to 240 VAC
Input
L
1
2.
Voltage selector
100 to 120
Close
terminals
200 to 240
Open
3. LG
4. GR
NC
5. 24 VDC output
NC
C200HW-PA209R: DC Input
L
/N
2
100 to 120 VAC/
1. AC Input
200 to 240 VAC
Input
L
1
100 to 120
2.
Voltage selector
Close
terminals
200 to 240
Open
3. LG
4. GR
RUN OUTPUT
250 VAC
7. RUN output
24 VDC
2 A
C200HW-PD024/
C200HW-PD025: DC Input
6. DC Input
24 VDC
3. LG
4. GR
/N (or L
/N if so indicated) terminal.
2
1
Section 2-2
L
/N
2
100 to 120 VAC/
200 to 240 VAC
Input
L
1
100 to 120
Close
200 to 240
Open
24 VDC 0.8 A
Output
L
/N
2
100 to 120 VAC/
200 to 240 VAC
Input
L
1
100 to 120
Close
200 to 240
Open
RUN OUTPUT
240 VAC
24 VDC
2 A Resistive
24 VDC
21