Specifications
Terminal Connections
(m + 1) words
24 VDC
24 VDC
Note 1. The polarity of the input power supply can be either positive or negative. The polarity of all commons for
CN1 and CN2, however, must be the same.
2. COM terminals for CN1 and CN2 must all be wired even though they are connected internally.
Transistor Output Unit C200H-OD218 (32 Points)
162
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
(m + 1) words
(m + 2) words
24 VDC
24 VDC
24 VDC
24 VDC
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
(m + 3) words
24 VDC
24 VDC
16 mA 4.5 VDC to 100 mA 26.4 VDC (see below)
None
0.1 mA max.
0.8 V max.
0.1 ms max.
0.4 ms max.
1 (32 points/common)
180 mA 5 VDC max.
3.5 A (The fuse is not user-replacable.)
110 mA 5 to 24 VDC10% min.
(3.4 mA × number of ON pts)
180 g max.
C-shape