Specifications
Terminal Connections
C200H-OD21A Transistor Output Unit (16 Points, Sourcing)
(Load Circuit Protection Provided)
Circuit Configuration
Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM
output becomes active (low level). The problem can be detected externally by connecting a DC Input Unit to
148
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1
L
3
L
5
L
5 to 24 VDC
7
L
9
L
11
L
NC
NC
COM
Max. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Load Short-circuit Protection
Power for External Supply
Weight
Alarm Output (See note 1.)
Reset Input
Load Short-circuit Protection
Dimensions
Output
indicator
2 kΩ
0
B0
L
A0
2
B1
L
A1
4
B2
L
A2
6
B3
L
A3
8
B4
L
A4
10
B5
L
A5
NC
B6
A6
B7
NC
A7
NC
B8
A8
B9
NC
+10%
24 VDC
/
, 1.0 A (4 A/Unit)
–15%
0.1 mA max.
0.8 V max.
0.1 ms max.
0.3 ms max.
1 (16 points/common)
160 mA 5 VDC max.
Detection current: 1.2 A min (1.6 A typical)
+10%
35 mA 24 VDC
/
–15%
400 g max.
No. of outputs: 1 (2 kΩ internal resistor),
Max. output current: 10 mA
Connectable Units: Only the following DC Input
Units can be connected:
C200H-ID001, ID211, ID212, IM211 (DC), IM212
(DC), ID215, ID501, MD115, MD215, MD501
Used when alarm output turns ON. Value will
depend on the external power supply. (See note 2.)
Detection current: 1.2 A min.
(1.6 A typical)
B-shape
to
0 V
Appendix B
min.