Omron C200HE-CPU42-E Instruction Manual page 205

Table of Contents

Advertisement

Specifications
Terminal Connections
NC
NC
+5 to 24 VDC
COM1
15
L
14
L
5 to 24
13
L
VDC
12
+
L
11
L
10
L
9
L
8
L
Note 1. I/O word "n" is determined by the unit number setting (n = IR 100 + 10 × unit number).
2. The Unit will have 16 static output and16 static input points when pin 1 of it's DIP switch is OFF.
3. When pin 2 of the Unit's DIP switch is ON, input points 08 to 15 in connector 2 are high-speed inputs.
12 VDC Input/Transistor Output Unit C200H-MD115
(Used as 128-point Dynamic Input Unit)
Output Specifications
(Connector 1)
Input Specifications
(Connector 2)
General Specifications
190
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
CN1
I/O word "n"
B
A
12
12
NC
11
11
NC
+5 to 24 VDC
10
10
COM0
9
9
7
8
8
L
6
5 to 24
7
7
L
VDC
5
6
6
L
4
5
5
+
L
3
4
4
L
2
3
3
L
1
2
2
L
0
1
1
L
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Fuses
Power for External Supply
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
No. of Circuits
Internal Current Consumption
Weight
Dimensions
CN2
I/O word "n+1"
A
0
1
1
2
2
3
3
12 VDC
4
+
4
5
5
+
6
6
7
7
8
COM2
9
10
NC
11
NC
12
NC
50 mA 12 VDC, 400 mA/common, 0.8 A/Unit
None
0.1 mA max.
0.7 V max.
0.2 ms max.
0.6 ms max.
2 (1 fuse/common; fuses are not user-replacable.)
45 mA 5 to 24 VDC10% min.
(2.8 mA × number of ON outputs)
12 VDC
10.2 to 13.2 VDC
2.7 kW
4.1 mA (at 12 VDC)
8.0 VDC min.
3.0 VDC max.
2 (dynamic, 64 points/circuit)
180 mA 5 VDC max.
300 g max.
130×34.5×100.5 (H×W×D, in millimeters)
Appendix B
B
8
1
9
2
10
3
11
12 VDC
4
+
12
5
13
+
6
14
7
15
8
COM3
9
10
NC
11
NC
12
NC

Advertisement

Table of Contents
loading