Omron C200HE-CPU42-E Instruction Manual page 169

Table of Contents

Advertisement

Specifications
Triac Output Unit C200H-OA224
Circuit Configuration
Internal
Circuit
Note 1. No blown fuse detector circuit is provided.
2. Check the fuse when there is no output.
Terminal Connections
154
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Max. Switching Capacity
Max. inrush current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Fuse: 3.15 A 250 V (5.2-dia.x20) MT4 (SOC)
250 VAC max.
(0.5 A max., 2 A/Unit)
0.5 A 250 VAC, 50/60 Hz (2 A/Unit)
10 A (pulse width: 100ms)
20 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
1.5 mA (120 VAC) max./3 mA (240 VAC) max.
1.5 VAC max. (50 to 500 mA)/5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency + 1 ms or less.
1 (12 points/common)
270 mA 5 VDC max.
3.15 A 250 V (5.2-dia.x20)
N/A
300 g max.
B-shape
OUT
L
OUT
L
Fuse
COM
250 VAC max.
0
B0
L
1
A0
L
2
B1
3
L
A1
L
4
B2
5
L
A2
L
6
B3
7
L
A3
8
L
B4
9
L
A4
10
L
B5
L
11
A5
L
B6
NC
A6
NC
B7
NC
NC
A7
B8
NC
COM
A8
B9
NC