Omron C200HE-CPU42-E Instruction Manual page 38

Table of Contents

Advertisement

Units
1, 2, 3...
20
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
• The following diagram shows the C200HW-PA204C.
3. Replacement Notification Module
4. TEST switch
1. POWER Indicator
The POWER indicator will be lit whenever the Power Supply Unit is output-
ting 5 V.
2. Terminals for External Connections
These terminals are connected as shown in the diagram below. The num-
bers in the diagram correspond to the numbers of the following items in the
description.
3. Replacement Notification Module (PA204C Only)
The seven-segment display on the Power Supply Unit indicates when
replacement is required.
4. TEST switch (PA204C Only)
The TEST switch can be used to temporarily turn OFF the alarm output
that notifies when replacement is needed.
Supply
Output
voltage
capacity
(see note)
100 to 120 VAC
5 VDC,
or 200 to
or 200 to
4.6 A, 30 W
4.6 A, 30 W
240 VAC
(Select the
voltage using
voltage using
the metal short
bar on the
bar on the
5 VDC,
voltage selector
9 A, 45 W
terminals.)
100 to 240 VAC
5 VDC,
(wide range)
4.6 A, 30 W
24 VDC
5 VDC,
4.6 A, 30 W
24 VDC
5 VDC,
5.3 A
26 VDC,
1.3 A,
40 W
Note The Power Supply Unit's internal parts may deteriorate or be damaged if the Unit
is used outside the power supply output capacity range for a long period of time
or if the output is short-circuited.
1. POWER indicator
2. Terminals for
Output
RUN
Replacement
terminals
output
Without
Without Without
24 VDC,
Without Without
0.8 A
Without
With
Without
Without
With
Without
Without
Without Display:
Supported
Output:
Supported
Without
Without Without
Without
Without Without
Section 2-2
external
connections
Model
notification
function
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200HW-PA209R
C200HW-PA204C
C200HW-PD024
C200HW-PD025

Advertisement