Power Supply Units with Replacement Notification
Precautions when Replacing Earlier Units
The following precautions apply when replacing a C200HW-PA204/PA204S/PA204R with a C200HW-PA204C.
Terminal Wiring
• Be sure to wire the ground terminals correctly. Incorrect ground terminal wiring will adversely affect the
Unit's resistance to noise. (For details on terminal arrangements for each Power Supply Unit, refer to
Part Names and Functions on page 19.)
• The C200HW-PA204C is not provided with a service power supply and RUN output (RUN).
Startup Time
• The time from when the power is turned ON until the PC operation starts is approximately 1 second fast-
er. Make sure that the system will not be adversely affected by the change in timing.
Power Failure Detection Voltage
• The power failure detection voltage is 85 V. The PC will stop operating if the voltage drops below this
voltage level.
Note If the previously used Power Supply Unit was used with 200 to 240 VAC, power failures were detected when
the voltage dropped to 170 V or lower and the PC operation stopped. With C200HW-PA204C, however,
operation will not stop between 85 V and 170 V. Therefore, make sure that the system will not be adversely
affected by the change in detection voltage.
Comparison between the C200HW-PA204C and the
C200HW-PA204
Item
Input specifications
Power failure detection voltage
Power supply startup time (See note.)
Service power supply
RUN contact output
Terminal block wiring
POWER indicator
Replacement notification
Note The time from when the external input (AC power supply) is input until 5 V or 26 V is output.
236
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
C200HW-PA204C
100 to 240 VAC (wide range)
85 V or lower
200 ms max.
Not supported
Not supported (for future expansion)
AC input
Alarm output
(replacement
notification
output)
Unconnected
terminals
On replacement notification module
Supported
(7-segment display + transistor
outputs)
Appendix E
C200HW-PA204 (Previous Unit)
100 to 120/200 to 240 VAC
(voltage selected)
100 to 120 VAC: 85 V or lower
200 to 240 VAC: 170 V or lower
1,500 ms max.
Not supported (Supported by the
PA204S)
Not supported (Supported by the
PA204R)
AC
Voltage
selector
Unconnected
terminals
On hood of Power Supply Unit
Not supported