Specifications
Triac Output Unit C200H-OA222V
Circuit Configuration
Note 1. No blown fuse detector circuit is provided.
2. Check the fuse when there is no output.
Terminal Connections
152
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Internal
Circuit
Fuse: 3 A 250 V (5.2-dia.x20) MQ4 (SOC)
250 VAC max.
(0.3 A max., 2 A/Unit)
0.3 A 250 VAC, 50/60 Hz (2 A/Unit)
10 mA (resistive load)/40 mA (inductive load)
10 VAC
3 mA (100 VAC) max./6 mA (200 VAC) max.
1.2 V max.
1/2 of load frequency or less
1/2 of load frequency or less.
1 (12 points/common)
200 mA 5 VDC max.
3 A 250 V (5.2-dia.x20)
N/A
400 g max.
B-shape
OUT
L
OUT
L
Fuse
COM
250 VAC max.
0
B0
L
1
A0
L
2
B1
3
L
A1
L
4
B2
5
L
A2
L
6
B3
7
L
A3
8
L
B4
9
L
A4
10
L
B5
L
11
A5
L
B6
NC
A6
NC
B7
NC
NC
A7
B8
NC
COM
A8
B9
NC
Appendix B