Technical Data; Ambient Conditions; Inputs And Outputs; Measurement - janitza Prophi Operating Instructions Manual

Reactive power controller
Table of Contents

Advertisement

Reactive Power Controller

Technical data

Weight
Combustion value

Ambient conditions

Overvoltage class
Pollution degree
Operating temperature
Storing temperature
Spurious radiation (residential areas):
DIN EN61326-1:2006, class B
IEC61326-1:2005
Sensibility to disturb. (industrial areas) :
DIN EN61326-1:2006, class A
IEC61326-1:2005
Sensibility to disturb. (industrial areas) :
DIN EN61326-1:2006, table 2
IEC61326-1:2005
Safety guidelines
:EN61010-1 08.2002
IEC61010-1:2001
Mounting position : any
Operating height
: 0 .. 2000m over NN
Humidity class
: 15% to 95% without dew
Protection class
: I =Device with protective wire
Protection class
Front
: IP65 according to IEC60529
Back
: IP20 according to IEC60529

Inputs and outputs

Tariff changeover
Current consumption
Switching outputs
Testvoltage against ground
Relay outputs
Switching voltage
Switching power
Max. switching frequency
Mechanical life expectancy
Electrical life expectancy
(Load = 200VA, cosphi=0,4)
transistor outputs
Switching voltage
Switching current
Max. switching frequency : 10Hz
1) Valid for current inputs >0.2A and in cos(phi) range 0,85 up to 1,00.
2) In the range of -10..18°C and 28..55°C an additional inaccuracy of +-0,2‰ of measured value per K must be respected.
3) Devices with option "RS485 interface" are only suitable for an ambient temperature of -10°C .. +50°C.
Page 54
: 1kg
:ca. 700J (190Wh)
: III
: 2
: -10°C .. +55°C
: -20°C .. +60°C
: about 2,5mA .. 10mA
: 2200V AC
: max. 250VAC
: max. 1000W
: 0,25Hz
: >30x10 6 switchings
: >7x10 6 switchings
: 15 .. 30VDC
: max. 50mA

Measurement

Measurement and supply voltage U: see type plate
Range for U
Prefuse
Power consumption
Rated pulse voltage
Tested voltage against ground : 2200V AC
Frequency of fundamental
Current measurement
Signal frequency
Power consumption
Rated current at../5A (/1A)
Minimum working current : 10mA
Maximum current
Overload
Measuring rate
Actualization of indication : 1 / second
Zero voltage release

Measurement accuracy

Voltage
Current
cos(phi)
Power
Frequency
Those specifications presuppose a yearly calibration and a preheating
of 10 minutes.
omr = of measuring range
omv = of measured value
= Key 1
= Key 2
: +10% , -15%
: 2A .. 10 A
: max. 7VA
: 4kV
: 45Hz .. 65Hz
: 45Hz .. 1200Hz
: about 0,2 VA
: 5A (1A)
: 5,3A (sinus shape)
: 180A for 2 Sec.
: 30(50) Measurement/Sec.
: < 15ms
: +- 0,5% omr
: +- 0,5% omr
1)2)
: +- 1,0% omv
: +- 1,0% omr
2)
: +- 0,5% omv
= Key 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents