Depending on the selected protocol the following settings may be partially deactivated:
11 BAUDRATE COM1
12 ADRESS COM1
13 Number MMI
14 Type of measuring device (MMI6000 / MMI7000 / MMI8003 / UCM-5)
15 Number of BR7000-1
16 ASCII transmit. interval
17 Separator (for ASCII )
An optional hardware-adapter „IF8000" extend the device with a 2nd interface COM2:
18 PROTOCOL COM2
19 BAUDRATE COM2
20 ADRESS COM2
21 Type of measuring device compare COM1
22 FUNCTION TI8004
23 Number of sensors [4]
24 - 36
Instructions for bus wiring when using the interface
For bus wiring screened cable has to be used!
R
The bus wirings (incoming and outgoing leads) always have to be applied directly to
R
the device (no branch boxes)!
In the devices at the end of the busses the terminating resistors integrated in the
R
device have to be activated (DIP-switch ON).
Connecting plan INTERFACE:
Switch for
terminating resistor
Baudrate 9600...256000 adjustable
Parity NONE, ODD, EVEN selectable
[1]
(1...255)
[1]
(1...9)
Number of connected MMI
(1...4)
Connected devices during cascading
[10] sec.
(1-255) Repeat. time ASCII transmission
Selection HT; LF/CR; SP; CR/LF; Minus; CSV
----
MODBUS KTR
MODBUS RTU
SYNC-MODE
EXTERN
TI8004
compare COM1
compare COM1
system-, unit- or step monitoring
(1...12)
compare application Ti8004
correlation step <--> sensor
Vb
Vm
L
N
L1
N
(L3) (L2)
On
INTERFACE RS 485
Gnd B
A PE
Prophi
OFF
Modbus monitoring
Modbus standard protocol
compare separate application
temperature interface
Im
SERVICE
k
l
EXT. IN-/ OUTPUT
ext. input
message-
110...230V
relay
12R / 12 RS
®
23