7.14.6 Modifications to the modules for class B

Building Technologies
Fire Safety
For the 'Ethernet switch (MM)' and 'Security module (firewall)' modules, the
following modifications are required to the wiring to reduce fault transmission from
limit value class A to class B:
For each electrical Ethernet connection, one ferrite core, type Würth Elektronik,
742 701 51
For each supply connection, one ferrite core, type Würth Elektronik, 742 715 4
P1
P2
L1+
M1
M2
L2+
RX
P1
P5
P2
TX
RX
P3
P6
P4
TX
L1+
M1
M2
L2+
Figure 80: Modifications to the wiring for class B