Pin Assignments - Siemens FS720 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Installing, exchanging and connecting modules
7
Installing the fiber optic cable network module

7.13.3 Pin assignments

7.13.3.1 Power A / B sockets and 'fault' relay contact
134 | 248
Building Technologies
Fire Safety
The 5-pin connector for the power supply is supplied with the fiber optic cable
network module.
Pin
Designation
1
+DC 9...30 V
2
-DC 9...30 V
3
COM
4
NO
5
NC
Relay contact open in normal operation
1
Relay contact closed in normal operation
2
Permissible conductor cross-section: 0.14...1.5 mm²
Power A (B)
9..30 VDC+
9..30 VDC-
COM
NO
NC
The power supply need not be monitored and made redundant when installing
in the fire control panel.
For remote installation, the power must be supplied by a power supply tested in
accordance with EN54-4 (e.g., FP120), which must be shielded and made
redundant.
Relay contact opens in the event of an error. The display indicates the error.
COM and NC (pin 5) are connected.
Description
Supply input +
Supply input -
Fault relay: Common contact (DC 24 V)
NO: Normally open
1
NC: Normally closed
2
1
2
3
4
2
5
A6V10210390_m_en_--
2018-08-29

Advertisement

Table of Contents
loading

Table of Contents