Shield connection terminal blocks [DE]

7.7 Shield connection terminal blocks [DE]

7.8 Loop extension

7.8.1 Installation

116 | 248
Building Technologies
Fire Safety
Figure 58: Mounting of the shield connection terminal blocks
1
Shield connection terminal block
2
Terminal strip
3
Philips screws M 3/6
Mounting steps
1. Fasten the terminal strip (2) using the two screws (3) as follows:
2. Eco and Standard housings: Above the rectangular cable breakout opening on
the right
3. Comfort housing: One terminal strip above each of the rectangular cable
breakout openings
4. Hang the shield connection terminal blocks (1) onto the terminal strip (2) and
fasten them by tightening the knurled screws.
The loop extensions (C-NET) FCI2003-A1 are mounted onto the periphery board.
The slots are located next to the corresponding detector line connections.
The installation of the two loop extensions on the periphery board (4-loop) is
identical.
Loop extension integrated line card 1:
Plug X15 / periphery board (4-loop)
Plug X15 / periphery board (2 loops)
Loop extension integrated line card 2:
Plug X25 / periphery board (4-loop)
2
1
A6V10210390_m_en_--
2018-08-29