7.25.1 Mounting on DIN rail or mounting plate
Building Technologies
Fire Safety
NOTICE
Short mounting distance
Module overheating
●
There must be an air gap of at least 1 cm above the cover cap of the module.
●
There must be a minimum distance of 1 cm between two modules or any
other object.
If you are installing the module without the housing, proceed as follows:
1. Use two screws to mount the module on a flat surface or use two mounting feet
FDCM291 to mount on a DIN rail.
The cover cap must be transparent to allow the LEDs to be seen at all times.
Pick a suitable mounting position, ensuring that the LEDs will remain visible at
all times during operation.
2. Connect the cables to the corresponding terminals. Only connect one wire per
terminal.
3. Fix the cables to the module by means of cable ties.
Figure 123: Mounting feet FDCM291
Figure 124: Mounting on DIN rail or mounting plate
Installing, exchanging and connecting modules
Modes of mounting for modules