6.2.1.2 X10, extinguishing terminal
Building Technologies
Fire Safety
5
8
1
4
Figure 26: Detailed view of terminal X10, extinguishing terminal
PIN
Designation
1
TERM_INT_VSYS+
2
TERM_INT_VSYS-
3
TERM_INT_DATA_A
4
TERM_INT_DATA_B
5
TERM_EXT_VSYS+
6
TERM_EXT_VSYS-
7
TERM_EXT_DATA_A Orange Data line A, secondary extinguishing
8
TERM_EXT_DATA_B Orange Data line B, secondary extinguishing
Admissible cable cross-section: 0.2...1.5 mm
X10
TERM_INT_VSYS
TERM_INT_VSYS
TERM_INT_DATA
TERM_INT_DATA
TERM_EXT_VSYS
TERM_EXT_VSYS
TERM_EXT_DATA
TERM_EXT_DATA
Observe polarity A/B
Max. length of line A/B, internal; 10 m (no EOL)
Mounting and installing extinguishing control panels
Card cage connections (1 sector exting.) FCA2046
X10
Color
Description
Green
Supply output (+), primary extinguishing
terminal
Green
Supply output (-), primary extinguishing
terminal
Green
Data line A, primary extinguishing
terminal
Green
Data line B, primary extinguishing
terminal
Orange Supply output (+), secondary
extinguishing terminal
Orange Supply output (-), secondary
extinguishing terminal
terminal
terminal
2
+
1
-
2
A
3
T
B
4
+
5
-
6
A
7
B
8
T1
T2
ext
int
T3
ext
ext
A6V10210390_m_en_--