Pin Assignments Version A4 - Siemens FS720 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Installing, exchanging and connecting modules
7
Power supply (150 W)

7.6.3 Pin assignments version A4

7.6.3.1 X1 mains connection
7.6.3.2 X8 output voltage
Pin
Designation
10
+B
I-begr.
9
+B
I-unbegr.
8
+24 V
7
+24 V
6
+24 V
5
+24 V
4
+24 V
3
0 V
2
0 V
1
0 V
106 | 248
Building Technologies
Fire Safety
Mounting steps
1. Position the luster terminal (3) in accordance with the dimensions (x) and (y)
and secure the luster terminal with the supplied adhesive mount.
2. Connect the assembled cable (4) to the luster terminal (3) and to the
connection terminal X11 (5) of the power supply according to the pin
assignment shown in the next chapter.
3. Secure the temperature sensor (NTC resistor) (2) directly next to the
batteries (1) as shown.
Secure the temperature sensor as close to the batteries as possible.
When using two power supplies (150 W) just one temperature sensor has to fitted
despite this.
Pin
Designation
1
PE
2
L
3
L
4
N
5
N
Admissible cable cross-section: 0.2...2.5 mm²
Description
Connection for battery, current limited via internal battery fuse F2 (without parallel
switching)
Connection for battery, no current limit (when switching in parallel, fuse in the
cable tree)
Supply output +24 V
Supply output +24 V
Supply output +24 V
Supply output +24 V
Supply output +24 V
Supply output 0 V
Supply output 0 V
Supply output 0 V
Admissible cable cross-section: 0.2...2.5 mm²
Batteries may be connected either on terminal 10 or, with external fuse, to
terminal 9.
Description
Earth (protective conductor)
External conductor (L1)
External conductor (L1)
Neutral conductor
Neutral conductor
A6V10210390_m_en_--
2018-08-29