Siemens FS720 Mounting & Installation page 52

Fire detection system
Table of Contents

Advertisement

Mounting and installing extinguishing control panels
6
Card cage connections (1 sector exting.) FCA2046
6.2.1.3 X11, outputs
52 | 248
Building Technologies
Fire Safety
Max. length of line A/B, external; 1200 m (EOL 120 Ω at furthest extinguishing
terminal)
A primary (internal) extinguishing terminal (T
A maximum of 5 secondary (external) extinguishing terminals (T
be connected
Observe address settings on the extinguishing terminal
Outputs 1...8 are 'open drain' driver outputs, not monitored, short-circuit-proof, and
protected against ground faults.
9
16
1
8
Figure 27: FCA2046 connection X11/1-8
PIN Designation
1
OUTPUT_1
2
OUTPUT_2
3
OUTPUT_3
4
OUTPUT_4
5
OUTPUT_5
6
OUTPUT_6
7
SUPPLY_25V8
8
SUPPLY_0V
Admissible cable cross-section: 0.2... 1.5 mm²
OUTPUT_1
X11
OUTPUT_2
OUTPUT_3
OUTPUT_4
OUTPUT_5
OUTPUT_6
SUPPLY_25V8
SUPPLY_0V
.) must always be connected
int
X11
Color
Description
Green
Output 1
Green
Output 2
Green
Output 3
Green
Output 4
Green
Output 5
Green
Output 6
Green
Supply output + DC 25.8 V
Green
Supply output – 0 V
1
2
3
4
5
6
+
7
-
8
.) may also
ext
A6V10210390_m_en_--
2018-08-29