7.24.2 Pin assignments

7.24.2.1 X1 supply input and sounder input from the periphery
X1 sounder module
Pin
Designation
1
+Vsys
2
Ground
3
Sound In +
4
Sound In -
7.24.2.2 X2 sounder 1 and 2 outputs
Building Technologies
Fire Safety
board
Description
Supply input from the
periphery board (+)
Supply input from the
periphery board (-)
Sounder input from the
periphery board (+)
Sounder input from the
periphery board (-)
Permissible conductor cross-section: 0.2...1.5 mm²
X1
Vsys
1
2
Ground
+
3
Sound In+
-
Sound In-
4
Pin
Designation
1
S2 out+
2
S2 out-
3
S1 out+
4
S1 out-
Permissible conductor cross-section: 0.2...1.5 mm²
X2
S2 out+
1
+
2
S2 out-
-
+
S1 out+
3
-
S1 out-
4
The terminating resistor of 3 kΩ has to be connected even when the output is not in
use.
Installing, exchanging and connecting modules
Periphery board
2 loops
Pin
Designation
X8-5
VSYS_01 (+)
X8-6
GND_01 (-)
X6-1
SOUND1+
X6-2
SOUND1-
Description
Sounder output 2 (+)
Sounder output 2 (-)
Sounder output 1 (+)
Sounder output 1 (-)
3
3
7
Sounder module
Periphery board
4 loops
Pin
Designation
X8-7
VSYS_01 (+)
X8-8
GND_01 (-)
X5-1
SOUND1+
X5-2
SOUND1-
203 | 248