6
Card cage connections (1 sector exting.) FCA2046
58 | 248
Building Technologies
Fire Safety
INPUT_MON_TYPE_1: 'Normally open'
INPUT_MON+
INPUT_MON-
Figure 32: MON_INPUT_TYPE_1, 'Normally open'
'Normally open'
Resistance range
0000...0249 Ω
0250...0519 Ω
0520...0799 Ω
0800...1099 Ω
1100...1499 Ω
1500...3999 Ω
≥4000 Ω
'Normally open', VdS-compliant
Resistance range
0000...0249 Ω
0250...0519 Ω
0520...0799 Ω
0800...1099 Ω
1100...1499 Ω
1500...3999 Ω
≥4000 Ω
Input status
SHORT (Fault)
QUIET
QUIET
ACTIVE 1
OPEN (Fault)
QUIET
OPEN (Fault)
Input status
SHORT (Fault)
QUIET
ACTIVE 1
QUIET
OPEN (Fault)
QUIET
OPEN (Fault)