Horizontal Terminations - 5" X 8" (127 mm x 203 mm) Rigid or Flex Pipe
The diagrams below show examples of horizontal termination arrangements using one, two, or three 90
1. A maximum of three 90
elbows are permitted.
o
2. Minimum distance between elbows is 1 ft. (305 mm).
Maintain clearances to combustibles as listed in the "Clearances" section.
Horizontal vent must be supported every 3 feet (0.9 m).
Firestops are required at each floor level and whenever passing through a wall.
Must use optional rigid pipe adaptor (part# 770-994) when using rigid pipe vent systems.
A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Flex system can only be used up to 10 feet (3 m) - otherwise, rigid venting must be used.

Horizontal Venting with Two 90

One 90
elbow = two 45
o
Option
V (min.)
A)
3' (914 mm)
B)
4' (1.2 m)
C)
5' (1.5 m)
D)
6' (1.8 m)
Restrictor Set 0 - Factory Setting

Horizontal Venting with Three 90

One 90
elbow = two 45
o
Option
V
(min.)
(max.)
A)
2' (610 mm) 2' (610 mm)
B)
3' (0.9 m)
2' (610 mm)
C)
4' (1.2 m)
3 (0.9 mm)
D)
5' (1.5 m)
4' (1.2 m)
E)
6' (1.8 m)
5' (1.5 m)
F)
7' (2.1 m)
6'(1.8 m)
Restrictor Set 0 - Factory Setting
H1

Elbows

o
elbows.
o
H + H1 (max.)
With these options, maximum total pipe length is 30 feet
(9.1 m) with minimum of 6 feet (1.8 m) total vertical pipe
4' (1.2 m)
and maximum 8 feet (2.4 m) total horizontal pipe.
5' (1.5 m)
A minimum of 1 ft. (610 mm) is required between
6' (1.8 m)
all 90
8' (2.4 m)
Elbows
o
elbows.
o
H
V + V1
H + H1
(min.)
(max.)
5' (1.5 m)
3' (0.9 m)
7' (2.1 m)
5' (1.5 m)
9' (2.7 m)
6' (1.8 m)
10' (3 m)
7' (2.1 m)
11' (3.4 m)
8' (2.4 m)
12' (3.7 m)
9' (2.7 m)
elbows.
0
With these options, maximum
total pipe length is 30 feet (9.1
m) with minimum of 12 feet
(3.7 m) total vertical pipe and
maximum 9 feet (2.7 m) total
horizontal pipe.
A minimum of 1 ft. (610 mm)
is required between all 90
elbows.
V
(Non Power Vent)
elbows (two 45
elbows equal one 90
o
o
0
H1
V1
City Series CP60E |
installation
elbow).
o
H
V
57