Operation
K1 "r1"
Display
FAC
r1
on
S.AL
FAC Factory settings
Cs
Customer settings
LED off
LED flashes
LED on
4.5.3
Activating or deactivating fault memory
Display
M
FAC Factory settings
Cs
Customer settings
4.5.4
Configuring interface
Display
Adr
0 / 3...90
FAC Factory settings
Cs
Customer settings
( )
Customer setting that is not modified by FAC.
4.6
Setting delay times and self test cycles (t)
Open menu "t" to configure the times.
Display
t
ton
toff
test
OFF/1/24
FAC Factory settings
Cs
Customer settings
24
isoES425_D00214_01_M_XXEN/10.2023
K2 "r2"
Cs
Display
r2
S.AL
FAC
Cs
off
Setting value
Range
FAC
3
Setting value
Range
FAC
0...10
0
0...99
0
0...99
0
24
FAC
Cs
ON
on
Memory function for alarm messages (fault memory)
Cs
(
)
Bus Adr.
Cs
s Start-up delay when starting the device
s Response delay K1 and K2
s Delay on release K1 and K2
h Repetition time for device test
LEDs
AL1
AL2
Device start with alarm
Description
Description
Adr = 0 deactivates BMS as well as Modbus
and activates isoData with continuous data
output (115k2, 8E1)
Description