7.2.3

Attaching surge killers to control equipment

If communication errors happen in synch with the on/off signals from certain control equipment (referred to
as "load" hereafter) such as no fuse breakers, electromagnetic contactors, relays, solenoid valves, and
induction motors, surge noise interference is suspected.
If this problem happens, keep the ground cable and communication cable away from the load.
If that is not possible, an installation of a surge killer will help reduce noise interference.
Place the surge killer as close to the load as possible.
Remedy for AC inductive load
Output
Output equipment such as PLC output unit
Remedy for DC inductive load
Output
Output equipment such as PLC output unit
Keep the ground cable and
communication cable away
from each other.
C
R
AC
Keep the ground cable and
communication cable away
from each other.
D
DC
L:Load
Place the surge killer near the load.
L:Load
Place the surge killer near the load.
7.2 Wiring inside and outside the panel
7.2.3 Attaching surge killers to control equipment
1
2
3
4
5
6
7
8
7 - 7