Download Screen

5.4 Download Screen
This screen is displayed during application/database/loop/LCD-160 downloads. The progress meter
shows the current download type and progress.

5.5 Application Corrupt Screen

During power-up, the panel checks the image integrity of the application code. If the code is
corrupt, the panel cannot proceed, and the following screen is displayed. The user must use VeriFire
to download the application code. Usually this screen results from a power interrupt during a
critical period of application download. The trouble LED will flash and the piezo (if enabled) will
pulse while this screen is in effect.
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
T R O U B L E
L O A D I N G . . N O S E R V I C E
L A K E V I E W G E N E R A L H O S P I T A L
B O O T L O A D E R
P E R F O R M D O W N L O A D
1 1 : 5 8 : 4 5 A W E D N O V 2 3 , 2 0 0 5
R E C E I V I N G L C M I M A G E . . .
7 6 %
Figure 5.8 Download Screen
T R O U B L E
E P R O M E R R O R
L A K E V I E W G E N E R A L H O S P I T A L
B O O T L O A D E R
1 1 : 5 8 : 4 5 A W E D N O V 2 3 , 2 0 0 5
A C K N O W L E D G E
Figure 5.9 Application Corrupt Screen