Honeywell NOTIFIER NFS2-3030 Programming Manual page 23

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

Panel Program
REMINDER MENU: Press this soft key to bring up the Reminder Menu screen.
ACCEPT: Press this soft key to save the information entered on this screen.
MORE: Press this key to progress to the second Panel Settings screen.
Soft Keys
LCM LOCAL MODE: Press this soft key to toggle between Yes and No. Enter Yes to enable all SLCs
to participate in local mode. When enabled, all LCMs will operate together in a limited fashion
when communication is lost with the NFS2-3030 CPU. Inputs on LCM loops (and associated LEM
loops, if installed) will activate outputs on all loops
• for those inputs and outputs that have been set with point programming to participate in local
mode, and
• when type codes are the same point type: that is, an input with a fire type code will activate an
output with a fire type code.(Refer to Appendix G, "Type Codes", on page 127 for point types).
Default: NO
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO
CAUTION:
!
On systems utilizing the DCC function, all locations that can participate in DCC should be set to YES.
LOCAL SETTINGS:Press this soft key to proceed to the Local Settings screen. Press the soft key
to scroll through the selections. The default is that there are no special local settings. Other settings
are explained in Appendix I, "Local Settings".
DEFAULT SETTINGS: Press this soft key to activate default settings for the following:
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
P A N E L S E T T I N G S
L C M L O C A L M O D E : Y E S
D C C P A R T I C I P A T I O N : N O
L O C A L S E T T I N G S
D E F A U L T S E T T I N G S
Figure 3.6 Panel Settings (2) Screen
Program setting for:
Local Control
Piezo
Proprietary Supervising
Station
Event Ordering
Display Address
LCM Local Mode
DCC Participation
A C C E P T
B A C K
Default:
Yes
On
No
USA
Yes
No
No
Program
23

Advertisement

Table of Contents
loading

Table of Contents