Point Program
Detector Occupancy Schedule
Soft Keys
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to place the cursor at the underlined
field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero
indicates no schedule is applied, and occupied detector sensitivity values are used.
ACCEPT: Press this key to accept the change made and return to the previous screen.
Detector Point Programming (3)
Press the MORE soft key on the Detector Point Programming (2) screen to display this screen.
Soft Keys
PREALARM: Press to select ALERT or ACTION for the Prealarm function. Refer to the section on
Prealarm in Appendix D, "Intelligent Sensing Applications" for a description of Alert and Action.
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
D E T E C T O R O C C U P A N C Y S C H E D U L E
W E E K L Y O C C U P A N C Y S C H E D U L E : 1 0
S U N D A Y
M O N D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
T U E S D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
W E D N E S D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
T H U R S D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
F R I D A Y
0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
S A T U R D A Y
0 8 : 0 0 - 1 2 : 0 0 ,
H O L I D A Y
U N O C C U P I E D
Figure 3.30 Detector Occupancy Schedule Screen
D E T E C T O R P O I N T P R O G R A M M I N G
P R E A L A R M : A L E R T
S I L E N C E A B L E : N O
Figure 3.31 More Detector Point Programming (3) Screen
-
-
-
A C C E P T
L 0 3 D 1 2 3
A C C E P T
Program
B A C K
B A C K
45