E.2: Equations; E.2.1: Arguments; E.2.2: Logic Equations - Honeywell NOTIFIER NFS2-3030 Programming Manual

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

CBE: Zones and Equations
E.2 Equations
Logic and Trouble Equations can define complex relationships between input and output devices.
The FACP supports up to 1000 Logic Equations, each designated with a Logic Zone number of
ZL1 through ZL1000. It also supports up to 100 Trouble Zones, each designated with a Trouble
Zone number of ZT001 through ZT100. Once created, these equations can be included in
input/output zone mapping.
1.
Equations will always begin with a logic function. The function set is listed below.
2.
Equations will be a maximum of 80 characters long, including parentheses and commas.
3.
Logic and Trouble Equations can have a maximum of 10 logic functions unless a time delay
function is used: a time delay function must be the only function in its equation.
4.
Equations are evaluated after all other devices have been evaluated.
5.
One logic equation can be used as an argument in another logic equation, or one trouble
equation can be used in another trouble equation, only if the equation used has previously been
evaluated; that is, only zones with a lower number than the zone currently being edited can be
used as arguments.
6.
A logic function can have a maximum of 20 arguments (inclusive start and stop address).
7.
Maximum for the delay timer is 23 hours, 59 minutes, 59 seconds (23:59:59).
Equations are entered using Point Programming for logic or trouble zones. Refer to these sections
in this manual for instruction. The panel will check for errors after the user has entered the
complete equation. Possible errors are too many or two few parentheses, too many or two few
arguments inside the parentheses, unknown function and unknown device type.
Equations are made up of two basic components: functions (either logic or time delay) and
arguments.
E.2.1 Arguments
Arguments are discrete parts of a logic or time delay function used in a logic or trouble equation.
They can consist of another function, another equation, or any of the the devices listed below.
E.2.2 Logic Equations
Logic Functions
The "AND" Operator
Requires that each argument be active.
Example: AND(Z02,Z05,L2D12)
All three arguments in the equation must be active for the logic zone to be activated
The "OR" Operator
Requires that any argument be active
120
LxxD1 - LxxD159
LxxM1 - LxxM159
(Nxxx)Z0 - (Nxxx)Z999*
ZF1, ZF2, ZF3, ZF4, ZF5, ZF9
T0 - T510
(Nxxx)ZT001 - (Nxxx)ZT100
(Nxxx)ZL1 - (Nxxx)ZL1000
xx = loop number (01 through 10)
(Nxxx) = Node number, necessary for CCBE programming. The node number identifies what
node the panel will watch for a particular zone activation.
Table E.2 Table of Arguments
detectors loop xx
modules loop xx
general zones
special zones
system troubles (trouble equations only)
trouble zones
logic zones
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Equations
(159 per loop)
(159 per loop)
(1000)
(6)
(511)
(100)
(1000)
.

Advertisement

Table of Contents
loading

Table of Contents