Honeywell NOTIFIER NFS2-3030 Programming Manual page 29

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

Panel Program
Soft Keys
ANNUNCIATOR TYPE: When the cursor is placed at the desired address, press this soft key to
scroll through the following list of types. Stop at the appropriate type.
Type
64PT
64SYS
*
64SVC
96PT
96SYS
96SVC*
96DCC
UDACT
TM4
AMG
FSCS
HVAC
UZC
* Two Level Bypass: When an ACS board is programmed as a 64SVC or 96SVC type,
† AMG Addressing: When using an AMG, the address it occupies (an address of 25
POINT PROGRAMMING: Press this soft key to proceed to the ACS Point Programming screen.
ACCEPT: Press this soft key to save all the changes made and return to the previous screen (Panel
Program).
ACS Point Programming
ACS Point Programming can be reached by pressing POINT PROGRAMMING at the ACS
Programming screen. This screen allows the programmer to assign a mode and sources to each
annunciator point at the annunciator address. One ACS input may be used to control multiple SLC
output modules by listing the output points in the SOURCE fields. This feature applies to the
following Types: 64PT, 64SYS, 64SVC, 96PT, 96SYS, 96SVC, and 96DCC.
NOTE: SLC output modules with releasing Type IDs may not be listed in the annunciator source
fields.
NOTE: The NFS2-3030 supports ACM-24AT/ACM-48A annunciators and their expanders with
either 64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 annunciators with
64 points at an address.
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Used for
64 point annunciation
64 point annunciation, with first 8 points reserved
64-point service mode for Two Level Bypass
96 point annunciation
96 point annunciation, with first 8 points reserved
96-point service mode for Two Level Bypass
96 point annunciation to be used with multiple Command Centers
UDACT, first address. Any additional UDACT annunciator addresses should be programmed as
64PT and be sequential.
TM-4
AMG
Smoke control modules set for FSCS mode
Smoke control modules set for HVAC mode
Universal Zone Coder, first address. Any additional UZC annunciator addresses should be
programmed as 64PT and be sequential.
the operator must enter the Program/Alter Status mode of operation before pressing any
push buttons to control points on these boards. If a push button is pressed while not in
the Program/Alter Status screen, and no unacknowledged events exist, the password
screen will automatically be displayed so the operator can enter the Program/Alter
Status mode.
through 32, typically address 32) must be set to annunciator type AMG, and address
one must be set to annunciator type 64PT.