G.5: Flashscan Codes - Honeywell NOTIFIER NFS2-3030 Programming Manual

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

Type Codes
HORN CIRCUIT
Y
AUDIBLE CKT
Y
SPEAKER
Y
blank
Y
NONRESET CTL
N
TELEPHONE
N
CONTROL NAC
Y
ISOLATED NAC
Y
ISOLATED SPK
Y
GEN ALARM
N
GEN SUPERVIS
N
GEN TROUBLE
N
GENERAL PEND
N
TROUBLE PEND
N
ALARMS PEND
N
INST RELEASE
N
REL. FORM C
N
RELEASE CKT
N
REL CKT ULC
N
REL END BELL
N
REL AUDIBLE
Y
FORM C RESET
N
*
Values represent program defaults
G.5 FlashScan Codes
This section provides a list of FlashScan Codes for FlashScan SLC devices. Select from these codes
to define the type of point:
130
N
Y
NAC
N
Y
NAC
N
Y
NAC
N
Y
NAC
N
N
Relay or NAC
N
N
Relay
N
Y
NAC
N
Y
NAC
N
Y
NAC
Y
Y
NAC
Y
Y
NAC
Y
Y
NAC
Y
Y
NAC
Y
Y
NAC
Y
Y
NAC
Y
N
NAC (SLC only)
Y
N
Form-C relay
(SLC only)
Y
N
NAC (SLC only)
Y
N
NAC (SLC only)
Y
N
NAC
Y
N
NAC
Y
N
Form-C Relay
(SLC only)
Table G.3 SLC Control Module Type Codes (2 of 2)
Label
Device/Point
FlashScan Codes
HEAT
FST-751/R, FST-851/R
ION
FSI-751, FSI-851
PHOTO
FSP-751,FSD-751P/RP, FSP-851, FSD-751PL/RPL, FSH-751
BEAM
FSB-200,FSB-200S
RFX SMOKE
SDRF-751
Table G.4 FlashScan Codes (1 of 2)
fire
Supervised NAC
fire
Supervised NAC
fire
Supervised NAC for speaker circuits
n/a
Supervised NAC for undefined device
n/a
Supervised output, unaffected by "System Reset"
command
fire
Supervised Telephone circuit
fire
Supervised NAC
fire
Supervised NAC for notification appliance, used
with audio isolators. Activates even if there is a short
on its NAC circuit. For ULC installations only.
fire
Supervised NAC for speaker circuits, used with
audio isolators. Activates even if there is a short on
its audio circuit. For ULC installations only.
fire
Control Module, XPC-8, or an XP5-C (in NAC mode)
configured as a Municpal Box Transmitter for NFPA
72 Auxiliary Fire Alarm Systems applications (MBT-
1 required). This Type ID can also be used for
general alarm activation.
supervisory
Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any Supervisory condition (includes
sprinkler type).
trouble
Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any System Trouble condition.This
device will not turn ON when it is in trouble (short or
open).
trouble
Control Module XPC-8 circuit, or an XP5-C (in NAC
mode) that will activate upon receipt of an alarm
and/or trouble condition, and remain in the ON state
until all events have been ACKNOWLEDGED. This
device will not turn ON when it is in trouble (short or
open)
trouble
Control Module or an XP5-C (in NAC mode) that will
activate upon receipt of a trouble condition, and
remain in the ON state until all troubles have been
ACKNOWLEDGED. This device will not turn ON
when it is in trouble (short or open).
fire
Control module or NAC for output that will activate
upon receipt of an alarm condition, and remain in
the alarm state until all alarms have been
acknowledged.
fire
Supervised for open circuits and ground faults.
Short = normal
n/a
Directs relay outputs to perform a releasing function.
n/a
Directs outputs to perform a releasing function.
n/a
Directs outputs to perform a release function as
required by ULC.
n/a
Activates NAC audio or visual device when
releasing circuits shut off.
n/a
Activates audio or visual devices steady when
releasing starts.
n/a
Control module used to interrupt 24V power to four-
wire conventional detectors for 30 seconds upon
reset. Used in conjunction with a monitor module
with a conventional detector Type ID
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
FlashScan Codes