Electrical
Main supply
Electric rating
Insulation class
Table 01
Technical data remeha Quinta 45 and 65

3.3 General Specification

(to be read with above table)
- One piece cast aluminium heat exchanger
- 1" BSP (f) and 1¼" BSP (m) flow and return connections
- ¾" BSP (m) gas connection
- Maximum operating pressure of 3.5 bar
- Maximum operating temperature of 95°C
- Low NOx (max 25 ppm, O
- Pre-mix, fully modulating (18-100%) gas burner with gas/air ratio control for maxi-
mum efficiency
- Intelligent advanced boiler control 'abc' c/w a comprehensive operating, service and
fault diagnostic facility
- Available for conventional flue or room sealed operation
- Capable of remote BMS (0-10V, on/off and High/low control options)
- Supplied fully factory assembled
- Powder coated enamel steel casing
- Suitable for use with a Natural gas or propane as standard (choices on commissio-
ning)
- Supplied as standard with safety interlock facility, temperature indication, control
and high limit sensors, common alarm and boiler run indication
- Efficiency of 99% at 80/60°C (Hi)
- Max efficiency of 110% (Hi) in fully condensing mode
- Manufactured to ISO 9001
- CE approved
V/Hz
W
IP
= 0%, dry)
2
12
Remeha
Quinta 45/65
230 / 1 / 50
30 - 85
30 – 90
20