GE ASTAT XT QT 0008U Series User Manual page 39

Solid state soft starter
Table of Contents

Advertisement

Function &
Default
PTC/NTC
Thermistor Type
PTC
Disabled,
Thermistor Trip
0.1–10Kohm
Disabled
10–120min.,
Undercurrent RST
Disabled.
Disabled
Store Settings
Fault Settings
• Control Keypad
39
Range
Unit
Sets input Thermistor Type
Measures the motor's thermistor resistance and trips the
ASTAT-XT when the level decreases below set level.
Sets ASTAT-XT's Thermistor Trip mode of operation.
Note:
Thermistor Trip has a factory preset time delay of 2 sec.
Sets ASTAT-XT's Undercurrent Reset time delay.
If the Undercurrent RST setting is OFF then ASTAT-XT will
not automatically reset after an Undercurrent Trip fault
occurs.
If you set the Undercurrent RST setting to a time value
then ASTAT-XT will automatically reset with a delay (the time
defined for Undercurrent RST). If the start command is not
removed, the motor will restart automatically after the delay
time.
During the delay time a message U/C Fault Retry In:
XX Min. is displayed.
Refer to section 4.7.2 on page 27 for details on setting of
Undercurrent Trip.
Same as Store Settings Main Settings on page 28.