Parameter
Last Fault
Motor FLT Current
Reserved
Thermal Capacity
Reserved
Actual_Data_Group
Example 1:
To read actual parameters 2 and 3 (Motor Current and Mains Voltage Actual Parameters, Addressed as 1 and 2) of
ASTAT-XT # 18 (its SERIAL LINK NO. = 18), the host computer should send following frame:
byte 1: Serial Link No.
byte 2: Function
byte 3: Starting Address High
byte 4: Starting Address Low
byte 5: No. of Points High
byte 6: No. of Points Low
byte 7: CRC_Low
byte 8: CRC_High
The ASTAT-XT response, when Current = 400 % of Im, and Voltage = 420V, is:
byte 1:Serial Link No.
byte 2: Function
byte 3: Byte Count
byte 4: Data High, parameter 2
byte 5: Data Low, parameter 2
byte 6: Data High, parameter 3
byte 7: Data Low, parameter 3
byte 8: CRC_Low
byte 9: CRC_High
Note:
$XX indicates Hexadecimal byte.
• Appendix A - MODBUS RTU Protocol
90
# (3x) # (4x)
24
280
25
281
26..36 282..292
37
293
38..108 293..364
109..128 365..384
($12)
($04)
($00)
($01)
($00)
($02)
($XX)
($XX)
($12)
($04)
($04)
($01)
($90)
($01)
($A4)
($XX)
($XX)
Comment
# of the fault that caused trip.
#
Fault
01
Over Temperature
02
Short Cir. Curr.
03
Overload
04
Under Current
05
Under Voltage
06
Over Voltage
07
Phase Loss
08
Phase Sequence
09
Shorted Scr
10
Long Start Time
11
Slow Speed Time
12
Wrong Connection
13
External Fault
14
Wrong Parameters
15
EMI/RFI Fault
16
Too Many Starts
17
Reserved
18
Thermistor.
19
Frequency
Current at trip time, % of Im.
Group of 20 actual parameters selected by
parameter settings 90..109
Another Possibility
(Modbus Plus users)
($00)
($02)
(400)
($01)
($90)
(420)
($01)
($12)
($03)
($01)
($01)
($XX)
($XX)
($12)
($03)
($04)
($A4)
($XX)
($XX)