Dip switches location, software version label location and PCB hardware version identification.

Dip Switch Settings on the Main PCB

5.5
The dip switch has eight separate switches. It is located under the front cover of the control module (models
QTx0085x-QTx1400) or under the display unit (models QTx0008x-QTx0072).
No.
Switch Function
1
Display format
2
Not Used
3
Mains/generator
4
Must be OFF
5
LCD language selection
6
7
Expanded settings
8
Software lock
Switch # 1 – Display Modes
5.5.1
Two display modes are available:
Maximized – display of all possible parameters.
Minimized – display of pre-selected parameters.
Setting switch # 1 to OFF will minimize the LCD displays.
Refer also to section 4.6 page 23.
Maximized Mode - Switch #1 – On
Display Only
Main Settings
Start Settings
Stop Settings
Dual Settings
Slow SP & Saving Parameters
Fault Settings
I/O Settings Parameters
COMM. Parameters
Statistical Data
• Installation
49
ASTAT-XT main PCB.
Switch Off
Minimized
-
Mains
-
See tables below section 5.5.4 page 50.
Disabled
Open
Minimized Mode Switch #1 – Off
Display Only
Main Settings
Start Settings
Stop Settings
Statistical Data
Switch On
Maximized
-
Generator
-
Enabled
Locked