Application 10
6.3.11 Application 10
System diagram 10A
Heat circuit 1
Heat circuit 2
Hot-water circuit
78
2 heat circuits and a hot-water circuit with direct control of storage tank.
The motor valve M1 controls the flow temperature, which is measured by the sen-
sor S1. The return temperature measured by the sensor S2 can be limited. The cir-
culation pump P1 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
The motor valve M2 controls the flow temperature, which is measured by the sen-
sor S4. The return temperature measured by the sensor S5 can be limited. The cir-
culation pump P2 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
ECL 2000 Type 1:
The motor valve M
(ON/OFF)
which is measured by the sensor S6. The actuator M
opens/closes completely upon receiving a relay signal from the controller. The
circulation pump P3 is not controlled by the ECL 2000.
EI.65.D4.02
performs on/off control of the storage tank temperature,
must be of a type that
(ON/OFF)