Configuring the ECL 2000
Sensors delivering a
0–10 V signal
28
A 0–10 V sensor is selected by setting Type to 0–10 V. This type of sensor can be
used for measuring:
Sun intensity
Wind velocity
Water flow
Energy
"Other".
When Type is set to 0–10V, 2 more parameters can be set: Amplific. and Offset.
The function of these is explained in the following.
Amplification, Offset
The sensor applies a voltage in the range 0–10 V to the controller's sensor input.
This voltage must be converted into the correct value. The parameters Amplific.
(amplification) and Offset are used to perform this calculation, as illustrated in
Figure 19.
Value [m/s, l/h, ...]
Offset
Figure 19. Amplification and Offset
The table below specifies ranges and default values of the parameters Amplific.
and Offset.
Sensor
Amplific.
range
0.00
Sun intens.
10.0
Wind veloc.
0.00
10.0
Water flow
0.00
10.0
0.10
10.0
EI.65.D4.02
Value = Amplification * Input + Offset
Amplific.
default
– 9.99
100
– 99.9
– 9.99
10
– 99.9
– 9.99
– 99.9
– 9.99
0.10
– 99.9
Input signal [V]
Unit
Offset
range
W/m²
± 0.00 – 9.99
(per V)
± 10.0 – 100.0
m/s
± 0.00 – 9.99
(per V)
± 10.0 – 100.0
l/h
± 0.00 – 9.99
(per V)
± 10.0 – 100.0
m³/h
(per V)