4.4 Pin Assignment

4.4.1 ECL 2000 Type 1, 230 V

Figure 11. Rear side, ECL 2000 type 1, 230V (white label)
I/O
I
II
III
I
II
S1-S7
S8-S9
!
Description
Relay output pump, 230V AC (NO)
Relay output pump, 230V AC (NO)
Relay output pump, 230V AC (NO)
3-point output motor valve
3-point output motor valve
Input: Pt 1000 temperature sensor
Input: Pt 1000, ESMF, 0-10V, pulse or digital
Note:
The LON bus connection (pin 1-2) is only active if the LON module has been fit-
ted in the controller.
EI.65.D4.02
Electrical Connections
Max. Load
4 (2)A 250V AC
4 (2)A 250V AC
4 (2)A 250V AC
0.15 A/250V AC
0.15 A/250V AC
13