Programming - ETC Echo Relay Panel Mains Feed Installation Manual

Table of Contents

Advertisement

Programming

The ERP-CI is programmable through the Echo Relay Panel user interface. This setting
determines how each relay responds to a dry contact input signal.
1. When in the Main Menu, select Arch Setup.
2. Within the Arch Setup menu, select Contact Inputs.
When the Contact Input card is installed, you will have the following options within the
Contact Inputs menu:
Contact displays the number of contact being configured, 1–24.
Space determines the space in which the selected action will happen.
On Open determines the action that occurs when the contact is opened. The following
options are available:
None (default): No action will be taken when the contact opens.
-
Off : Off will be activated in the selected Space when the contact opens.
-
Preset : The selected Preset will be activated in the selected Space when the contact
-
opens.
Sequence : The sequence configured for the selected Space will be activated when the
-
contact opens.
Output to Full : When you select this option, you are able to select a range of Outputs on
-
the bottom line of the Contact Input screen. The selected range of Outputs will be
driven to full when the contact opens.
Output to 0% : When you select this option, you are able to select a range of Outputs
-
on the bottom line of the Contact Input screen. The selected range of Outputs will be
driven to 0% when the contact closes.
On Close determines the action that occurs when the contact is closed. The same actions
are available as listed for On Open, above.
For additional information on Contact Input card setup and programming, see the Power
Control Processor Mk2 Configuration Manual which is available for download at
etcconnect.com.