Data And Control Wire Specification; Dmx Control Wiring And Termination - ETC Echo Relay Panel Mains Feed Installation Manual

Table of Contents

Advertisement

Data and Control Wire Specification

Purpose
DMX In and
DMX Pass-Thru
(J8 and J9)
Ethernet (RJ45
connection)
Emergency In and
Out
UL 924 emergency
contact input
(J2 and J3)
Contact Input
Option Card
0–10V Option Card
DALI Option Card
*See the white paper Understanding 0-10V LED Drivers for Class 2 and Class 1 wiring
considerations.

DMX Control Wiring and Termination

Follow the DMX termination kit instructions provided with the product to terminate the
control wiring.
DMX termination is made to J8 and J9 on the termination board. Use the DMX Pass-Thru if you
are daisy-chaining to another panel or DMX device.
After completing the DMX data connections, you must
properly terminate the DMX line using the termination
switch (S2) on the relay panel termination board. Data
termination eliminates reflections at the end of the
DMX data run.
Note:
The RDM position is not used.
29
Recommended Cable
Belden 9729 (or equivalent)
Belden 1583A (Category 5e or
better)
2
1.5–2 mm
(16 AWG), twisted
pair
2
0.5–4 mm
(18–12 AWG)
Class 2 wire
2
0.25–4 mm
(24–12 AWG)
Class 2 or Class 1 wire*
2
0.25–4 mm
(24–12 AWG)  Class
2 or Class 1 wire*
Notes
DMX is RS485 serial and must be
installed in series (i.e., daisy-chain)
topology.
RJ45 connection per EIA/TIA 568B.
Test to TSB 67 standards.
Contact input for UL 924
emergency lighting loads.
Maximum of 24 individual dry
contacts terminate to a removable
pluggable connector. Option card
connects to the termination I/O
board.
Maximum of 50 ballasts (400 mA)
per channel. Option card connects
to the termination I/O board.
Maximum of 64 ballasts per loop.
Option card connects to the
termination I/O board.
that is physically connected
Relay Panel Mains Feed Installation Manual
Turn on DMX termination
in the last panel/device
in the DMX chain.

Advertisement

Table of Contents
loading

Table of Contents