ETC ALCR-DIN Installation Manual
ETC ALCR-DIN Installation Manual

ETC ALCR-DIN Installation Manual

Automatic load control relay
Hide thumbs Also See for ALCR-DIN:

Advertisement

Quick Links

E T C I n s t a l l a t i o n G u i d e
Automatic Load Control Relay
Overview
The Automatic Load Control Relay (ALCR) is a UL 924 listed device that is powered
from an emergency source and provides power to emergency lighting load(s). The
ALCR ensures a "lights on state" during loss of normal power while tracking the state of
normal lighting loads during normal operation. The ALCR also assures a "lights on"
override by utilizing a normally closed emergency contact closure which interfaces with
fire alarm and emergency systems.
The ALCR is available in two models for installation convenience including Power Pack
(ALCR-PP) and DIN-rail (ALCR-DIN).
Electrical Specifications
Rated for indoor use only. UL, cUL listed Emergency Lighting and Power under
UL 924 at line voltages of 120 and 277 VAC, 60 Hz.
• Load ratings include:
• Ballast loads, 20A maximum at 120 or 277 VAC
• Incandescent loads - 10A maximum at 120 or 277 VAC
• Provides remote activation by dry contact closure for connection to a fire alarm or
building management system.
• ALCR-DIN model only provides auxiliary contact for 0-10 Vdc/ Fluorescent ballasts.
WARNING:
Corporate Headquarters
3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA
London, UK
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK
Rome, IT
Via Pieve Torina, 48, 00156 Rome, Italy
Holzkirchen, DE
Ohmstrasse 3, 83607 Holzkirchen, Germany
Hong Kong
Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong
Service: (Americas)
service@etcconnect.com
Web:
www.etcconnect.com
Copyright © 2014 ETC. All Rights Reserved.  Product information and specifications subject to change.
7180M2150  Rev G  Released 2014-07  ETC intends this document to be provided in its entirety.
Autom atic Lo ad C ont rol R el ay
ALCR-PP
Risk of electric shock! The ALCR utilizes high voltage and should only be
installed by a qualified installer or electrician. Follow all local codes for
installation and follow the proper lockout/tag out procedures per NFPA
Standard 70E.
Tel +39 (06) 32 111 683
Tel +49 (80 24) 47 00-0
(UK)
service@etceurope.com
Pa ge 1 of 8
ALCR-DIN
Tel +44 (0)20 8896 1000
Fax +44 (0)20 8752 8486
Fax +49 (80 24) 47 00-3 00
(DE)
techserv-hoki@etcconnect.com
El ect roni c Th eatre C ontro ls, In c.
Tel +608 831 4116
Fax +608 836 1736
Fax +44 (0)20 8896 2000
Tel +852 2799 1220
(Asia)
service@etcasia.com

Advertisement

Table of Contents
loading

Summary of Contents for ETC ALCR-DIN

  • Page 1 Copyright © 2014 ETC. All Rights Reserved.  Product information and specifications subject to change.  7180M2150  Rev G  Released 2014-07  ETC intends this document to be provided in its entirety. Autom atic Lo ad C ont rol R el ay Pa ge 1 of 8 El ect roni c Th eatre C ontro ls, In c.
  • Page 2: Installation Requirements

    Reference "Installation and Termination of the ALCR-PP". The ALCR-DIN (DIN-rail) model is designed to be permanently installed on a consumer DIN rail 35mm (complies with DIN43880 and EN60715). Reference "Installation and Termination of the ALCR-DIN"...
  • Page 3 E T C I n s t a l l a t i o n G u i d e Automatic Load Control Relay Step 1: Locate the normal and emergency circuit breaker panels and turn off the power to the circuits. Step 2: Remove face plates and other hardware from the junction box, gaining access to the high voltage wiring.
  • Page 4: Installing A Re Mote Activation Input To The Alcr-Pp

    The remote device that triggers the Emergency circuit “On” must provide a normally closed, maintained dry contact closure for fire alarms, etc. When the remote device is activated, the contact closure opens and the contacts force the ALCR-PP into the emergency “On”...
  • Page 5 Connect the Neutral for the emergency circuit to the Emergency Neutral screw terminal as shown. Step 3: Connect the ALCR-DIN to the normal lighting and control device for the area controlled. Reference the wiring diagram on the previous page. Connect the normal lighting circuit to the Normal Power Sense, Normal Switch Sense, and Normal Neutral screw terminals as shown.
  • Page 6: Installing A Re Mote Activation Input To The Alcr-Din

    Remove the factory installed jumper from the Remote Loop In and Remote Loop Out terminals. Step 3: Connect the Remote Loop In and Remote Loop Out terminals on the ALCR-DIN to the single pole contacts on the remote device or test switch. Step 4: Continue to "Remote Activation Test"...
  • Page 7: Power Up And Test

    Power Up and Test Initia l Te st Initial testing of the ALCR function should be done with the Remote Loop In and Remote Loop Out jumper installed on the ALCR-DIN and the blue loop uncut on the ALCR-PP. Step 1: Turn On the circuit breaker in the emergency panel for the controlled circuit.
  • Page 8: Examples Of Use

    Emergency Light Fixture Emergency Neutral (Gray) 0-10V common 0-10V 0-10V signal 0-10V signal controller 0-10V Fixture Control (ALCR-DIN only) Remote 0-10V / Loop • When normal power is present and switch is closed, both 0-10V controlled fixture(s) dim. UTOMATED ONTROL ELAY •...